Monitoring temperatures of the hot face of the refractory in Claus Thermal Reactors is done mainly for two reasons:
There are essentially two types of devices suitable for monitoring the temperature of Claus Thermal Reactor refractory. These are the Thermocouple and the Infrared Radiation Pyrometer. Although both have proven to be effective over many years of Claus Reactor service, both technologies are encumbered with drawbacks and operational problems.
Thermocouples
Thermocouples
are the standard industrial temperature measurement method that has proven to
generally be the most cost effective, accurate and reliable technology for over
100 years. Thermocouples, while normally requiring no periodic maintenance,
have gained a reputation in Claus Thermal Reactor service as being unreliable.
This is considered to be an unfair assessment by some designers. Nevertheless,
"thermocouple technology", per se, suffers with this reputation, which
has primarily arisen from the attempted use of modified standard industrial
thermocouple designs, which are unsuitable for this service.
Thermocouple design advancements have overcome the problems associated with corrosion and high temperature found in Thermal Reactors. The thermocouple still has a lingering poor reliability reputation with some users. There are still some failures, which are normally the result of improper installation. Such failures result from shifting refractory, damaging the protective well. Such damage exposes the metallic thermocouple element to corrosion and eventually causes it to fail. Choosing a large refractory well thermocouple specifically designed for Claus Thermal Reactors, installing it properly and operating it within the published guidelines will provide accurate temperature measurement for years with no maintenance. (Fig. 1)
For a period of time following the
breakage of a thermocouple protective well, the operator of the reactor may
not be aware that thermocouple corrosion has begun. Thermocouple failure can
be a slow process. As the corrosion progresses, the T/C output signal will gradually
drop relative to the actual temperature. This "low" error may allow
the reactor to be operated at undetected higher and higher temperatures.
This potential error problem has been solved by a thermocouple design enhancement
that provides a "self-monitoring" feature that warns of a failing
T/C element. This new design incorporates two separate independent operating
thermocouples, a primary and secondary. (Fig. 2). The primary one is installed
in the conventional position inside the element well and is constantly flushed
with N2 or clean, dry instrument air and provides the fast response needed for
operations. The secondary T/C is installed adjacent to the primary T/C, but
it is embedded in a solid ceramic-blend sealant material. It is not exposed
to the flush gas or to the reactor gases if the thermowell becomes damaged.
The secondary T/C output signal is the "reference" signal and because
it is embedded in solid ceramic material, is slower to respond than the primary
T/C element and therefore it is not suitable for use as the primary operating
measurement.
In
the event of a mechanical failure due to improper installation, shifting refractory
or thermal shock severe enough to break the element protective well, the primary
thermocouple element would be exposed to the reactor gases. Gradually, the now
exposed primary element would become corroded and its output signal would slowly
begin to drop relative to the actual reactor temperature. On the other hand,
the secondary T/C, which is encased in a solid ceramic sealant material, would
be shielded and therefore become contaminated at a far slower rate than the
"exposed" primary thermocouple. This makes the secondary thermocouple
relatively immune to the corrosive gases and permits it to provide an accurate
output signal for a considerable period of time after contamination of the primary
element has begun. Therefore, in the event of a thermowell failure, the two
output signals would show an increasing deviation from each other. This deviation
in output signals provides a warning that corrosion has begun on the primary
thermocouple element and that it is necessary to plan to begin to use alternate
temperature monitoring methods, such as other thermocouples, infrared or even
analyzers.
This
new thermocouple design warns of inaccuracy and prevents the operator from relying
on a failing thermocouple's gradually diminishing output signal. This prevents
false low readings, which can allow undetected high temperature to damage the
refractory.
Another new thermocouple development is the addition of a third thermocouple element, which is used as a "refractory dry out" temperature sensor. (Fig. 3) This very accurate thermocouple element, usually a "T" type, is used to measure the critical low temperatures (usually 658C to 3008C) required to properly cure the newly installed refractory material. This additional thermocouple element provides an easy means to accurately monitor this temperatures without having to install additional thermocouples or to change wiring as the reactor is brought up to operating temperature. As the "dry out" is completed and the reactor operating temperatures are reached, this thermocouple element burns up without damaging the other elements. The advantage of this third thermocouple is that it permits accurate control of the refractory dry out cycle and reduces costs during the startup period. With the new thermocouple, all three, the primary, secondary and the dry out T/C's are all permanently wired through the assembly's conduit head, eliminating the need to install temporary wiring for "dry out". This simplifies the installation and avoids the need to later remove the exposed wiring under operating conditions.
Improper
installation practices have been identified as the primary reason that the otherwise
suitable thermocouple designs sometimes suffer a relatively short life. Research
and development efforts have developed methods to improve the quality of thermocouple
installations. The main problem with thermocouple installations has been the
creation of the "bore-hole" through the refractory below the mounting
nozzle. For many years, an installation "mandrel" (Fig 4) has been
the only tool available for creating the proper bore size, centering the hole
in the nozzle and maintaining the alignment of the hole relative to the mounting
flange. The mandrel is bolted onto the mounting flange prior to installing the
refractory; the refractory is then installed in the normal manner around the
protruding tube that extends down into the reactor. As soon as the refractory
sets, the mandrel is removed, leaving a proper bore hole for the thermocouple
installation
A
recent modification to the mandrel design incorporates an adjustable "Stop-Disc"
that is used to keep refractory castable and mortar from entering the base of
the nozzle and upsetting the critical dimensions that are required for successful
thermocouple installation. If castable refractory material is permitted to enter
the base of the nozzle, the top surface of the refractory will extend up beyond
the vessel shell. If this condition is not corrected, the refractory well will
not be installed in the proper position, causing interference with the element
well and probable failure of the element well during installation or startup
In recent years, refractory installers have preferred to drill the bore hole through the refractory instead of mounting the mandrel, which requires that the refractory brick be cut and fitted around the mandrel pipe.
But, it has been found that creating a "drilled" hole that is on-center, straight, uniform and of the proper bore size, is very difficult to achieve. Boring an incorrect hole through the refractory is very likely to cause the thermocouple assembly to become broken by shifting refractory, which will result in early failure. Also, once an improper hole is cut in the refractory, it is very difficult, expensive and time consuming to correct it.
To
assure proper drilling of the refractory, a new "Drill-Guide" is now
available (Fig. 5). The "drill-guide" is mounted to the nozzle flange.
The refractory core drill is inserted down inside the guide pipe, which extends
down into the nozzle to within approximately 25-mm of the refractory. The guide
pipe is slightly larger than the drill size, which is typically 2.25 inches
(approximately 60-mm). At the top, a drill shaft centering guide is adjusted
to help keep the drill bit aligned so that a straight perpendicular bore hole,
located in the exact center of the nozzle is created. Proper positioning of
the hole insures that shifting refractory will not place high stress loads on
the protective well. When the installation is to be made in new refractory,
the "stop-disc" is used to keep the castable refractory or mortar
from entering the nozzle.
After proper installation, the only operating requirement is that N2 or clean dry instrument air flush gas pressure and flow is maintained through the thermocouple. Although the element protective well is designed to be "gas-tight", certain ions and elements may migrate directly through the wall of the thermowell at high temperatures and if not flushed out, will +accumulate and eventually corrode the thermocouple elements. To assure that the necessary flush gas hardware is provided and installed in the proper manner, a pre-piped flush gas panel is now available (Fig. 6). This panel not only provides the necessary components to measure and control the pressure and flow of the flush gas, but also assures that the proper piping and connections are in place. Without the proper flush gas installation and operation, contaminants will enter through the wall of the thermowell and eventually corrode the thermocouple element causing inaccuracy and ultimate failure.
The use of Claus Thermal Reactor
"large-refractory well" type thermocouples with self monitoring primary
and secondary thermocouple elements, properly installed and operated, will provide
years of accurate maintenance free temperature measurement. (Fig. 7)

Infrared
Infrared has become a very popular means to monitor Claus Thermal Reactor temperature.
The main reason is that it does not come in contact with the hot corrosive reactor
gases. Nor is it installed in a manner whereby it may be damaged by shifting
refractory. On the other hand, Infrared technology suffers from certain drawbacks.
The primary ones are that it is expensive, is not inherently accurate in the
Claus environment and can require hazardous, costly and frequent maintenance.
Also, the IR cannot measure the low temperatures required during the refractory"dry
out" and curing phase.
The primary difference between the thermocouple and the IR device is that the IR device does not inherently measure temperature. Instead, it measures the intensity of radiated energy, and as such, it infers the temperature measurement. What this means is that the IR device must be "told" what the actual temperature is and then the IR will measure the deviations from that selected temperature as long as the operating conditions do not change.
The main maintenance and error problem of the IR is that the sight path into the reactor can become occluded or blocked, either from condensed sulphur vapors collecting on the viewing window or by the vessel nozzle becoming filled with particulate matter over time. Such things as refractory emissivity and the mix of the reactor gases also effect accuracy of the IR device. Another problem is variable absorption of the radiation by the reactor gases. The commonly used lead sulfide IR sensors, associated electronics and mechanical choppers cannot withstand the high ambient temperatures of the vessel and mounting nozzle, requiring that the instrument, lens assembly and the nozzle be cooled with water and a high volume of purge gas. This lead sulfide type sensor also "ages" causing it's output signal to drift over time, resulting in varying degrees of inaccuracy in the readings.
To control the problems associated with obscured sight paths, it is necessary to periodically clean the nozzles and the lens assemblies. To perform this task, the nozzle block valve is closed, the lens assembly removed and a seal-gland equipped cleaning rod assembly is mounted on the nozzle. The rod is used to physically push the material out of the nozzle and into the reactor while it is operating. Then the rod assembly is removed and a similarly mounted rod-type thermocouple is inserted into the reactor to obtain the actual temperature at the base of the nozzle. The lens assembly is cleaned and then reassembled. The IR unit is then manually adjusted to provide an output signal that matches the temperature measured by the inserted thermocouple. This is accomplished by adjusting an "emissivity" control, which corrects for instrument aging changes, changes in the surface of the refractory or changes in the composition of the gases. Note that this "inserted" thermocouple can only be inserted a distance just beyond the base of the nozzle near the refractory hot face; it cannot be placed against the other side of the vessel from which the IR energy is being radiated. Therefore, there is no way to verify an accurate temperature of the face of the refractory on the opposite side of the reactor (unless, of course, a thermocouple is installed in that location).
This type of maintenance requires
the utmost in safety precautions and is expensive. Corrosive gases attack the
stainless steel jacket of the inserted thermocouples, which are sacrificed with
each insertion. The "inserted" thermocouple recalibration effort only
resets the accuracy of the IR device at one specific temperature; IR suppliers
typically recommend that the instruments be periodically removed and returned
to the factory for full range and linearity re-calibrations. These expensive
full range calibrations are performed in a black body furnace, which provides
a perfect emissivity environment and corrects the signal over the entire measurement
range. However, when the IR instrument is again reinstalled in the reactor,
it must again be manually reset to a temperature measured by a thermocouple
inserted into the nozzle. This is because the factory is unable to calibrate
the unit under the exact same conditions that exist in that particular location
in that particular Thermal Reactor using the same exact gas composition.
A new IR technique has been developed to minimize or perhaps completely eliminate these drawbacks. This new technique employs four distinct features:
Periodic recalibration is unnecessary with the use of the silicon technology sensor. This sensor is superior to the lead sulfide type technology in the Claus application because it does not exhibit the same tendency to drift, age and become inaccurate over time. However, the silicon type sensor cannot withstand the high temperatures encountered at the mounting flange of the reactor nozzle. Typically, temperatures at the nozzle may reach up to 1758C. It is for this reason that the sensor / electronics unit is mounted separately from the reactor nozzle and connected to the viewing lens via a special fiber optic cable. This installation permits the sensor and electronics to operate in a suitable environment and eliminates the need to cool the reactor nozzle or the instrument. (See Fig. 8)

Cooling of the nozzle encourages the sulphur species to condense onto the viewing window, which blocks the sight path of the IR sensor. If the viewing window were maintained at a higher temperature, sulphur vapors would remain in a gaseous state and not precipitate onto the viewing lens or inside the nozzle.
Remotely mounting the IR sensor and electronics not only protects the electronics from the excessive heat, but also permits the lens assembly to operate at even higher temperatures than those normally occurring in the nozzle. Adding heat to the nozzle solves the problem of obscured sight paths. This higher temperature insures that sulphur cannot precipitate onto the viewing window surface or plug the nozzle.
To maintain the proper amount of heat, a new design IR nozzle adapter incorporating a steam jacketed window assembly, is maintained at approximately 150°C, well above the temperature where sulphur will precipitate onto surfaces. Maintaining this high temperature causes the sulphur to remain in the gaseous state and not collect on the viewing window or precipitate into liquids or solids that will accumulate in the nozzle. A purge flow is maintained at the base of the lens assembly to discourage particulate matter from collecting in the nozzle. This purge flow is also heated.
A steam jacketed fiber optic cable adapter is mounted to the nozzle. Heat is maintained by routing 50# steam through the nozzle jacket. The fiber optic cable and lens assembly, which routes the IR infrared radiation to the remotely mounted sensor, is capable of withstanding 2008C.
Field tests to date have shown that this combination of the remote-mounted silicon sensor with the steam jacketed nozzle window prevents buildup of sulphur on the window assembly. Other purged nozzles on the same reactor did accumulate a buildup of sulphur that would have partially occluded the IR's view and cause a reading error. The silicon sensors combined with the use of fiber optic cable have exhibited no temperature deviations compared with adjacent thermocouples. No maintenance or recalibration has been required.
This change to the silicon "non-drift" electronics technology, coupled with the high temperature window design solves most of the maintenance problems and improves long term accuracy.
* * * * * * * *
It is recommended that both Infrared and Thermocouples be employed in measuring
Claus Thermal Reactor refractory temperature. The reason is that upsets or conditions
that may cause failure of a thermocouple would likely not have any harmful effect
on an Infrared unit. Similarly, the conditions that may cause the Infrared to
become inaccurate will likely have no effect on the thermocouple. Thermocouples
are inherently accurate and do not rely on manual "calibrations" or
"adjustments" to maintain correct readings. The combination of thermocouple
and infrared radiation sensing provides the utmost in reliability and accuracy.
The operator has a good reading and something to which it may be compared.
It is well recognized that the measurement
of the temperature of the hot face of the Claus Reactor refractory is one of
the most severe and demanding applications in industry. By addressing each of
the unique characteristics of this difficult measurement, accurate and reliable
monitoring can be done at a relatively low cost.
Summary:
To achieve the lowest overall cost, highest reliability temperature measurement capabilities